• Improved connection ease with a greater number cable glands; 3 x M25 style and 2 x M20 style;
• Improved switching flexibility with up to 6 fully configurable switches;
• New and improved swing out case design allows for easy cable connection, switch configuration and testing without removal of the cover;
• Up to 6 fully independent switches flexible enough for most control and alarm schemes;
• Each switch can be specified by switch type, hysteresis range, and set point, without limitation of sequential set points;
• Standard switch rated for up to 15 Amps AC and up to 10 Amp DC, switches also available for higher VDC (magnetic blow out, M.B.O.), and switches for milliamp loads;
• Various analog outputs also available (mA, Pt 100, and Cu 10);
• Each switch can be specified with adjustable hysteresis (5 to 25°C);
• Non-pressured bellows system better resists leakage when compared to bourdon tube (pressurized) style capillary thermometers;
• Integrated heating element in bellows for winding temperature indication eliminates extra cost and complexity of accessories to simulate the winding;
• AKM bellows system provides a 260° dial deflection (angle the pointer travels from minimum to maximum) making it easier to interpret temperature reading from a distance. OPTIONS - Temperature ranges applicable for oil (liquid) or winding (winding temperature simulation does not require heated well);
• Up to 6 user adjustable switches with independent switch types;
• Mounting style, tank connection style, probe length, capillary (length, material, protective housing), compatible well (pocket);
• SCADA outputs (0-1mA, 4-20mA, Pt 100, and Cu 10), analog and digital remote indicators.