ELECTRICAL ASSET MANAGEMENT & PROTECTION

MEASUREMENT, MONITORING, TESTING AND PROTECTION SOLUTIONS FOR ELECTRICITY NETWORKS

AKM OTI/WTI Remote Mount Thermometers

Capillary based, mechanical, remote indicating thermometer. Configurations for oil temperature measurement and winding temperature simulation. Features up to 6 adjustable switches for alarm, trip, and cooling system functions and can be equipped with various electronic outputs for SCADA and remote monitoring applications.

Print Tell a Friend

features

• Billed as the next generation thermometer from the global leader;
• AKM bellows measurement with resettable maximum pointer;
• Up to 6 fully independent and user adjustable switches (contacts) for control and alarms; • Mounting style, tank connection style, probe length, capillary (length, material, protective housing), compatible well (pocket).
• SCADA outputs (0-1mA, 4-20mA, Pt 100, and Cu 10), analog and digital remote indicators; • Application of the product allows accomplishment of the most demanding alarm and control configurations;
• Failure costs can be reduced by using the reliable AKM bellows operation;
• The all in one design results in a simplified installation process.

technical

• Improved connection ease with a greater number cable glands; 3 x M25 style and 2 x M20 style;
• Improved switching flexibility with up to 6 fully configurable switches;
• New and improved swing out case design allows for easy cable connection, switch configuration and testing without removal of the cover;
• Up to 6 fully independent switches flexible enough for most control and alarm schemes;
• Each switch can be specified by switch type, hysteresis range, and set point, without limitation of sequential set points;
• Standard switch rated for up to 15 Amps AC and up to 10 Amp DC, switches also available for higher VDC (magnetic blow out, M.B.O.), and switches for milliamp loads;
• Various analog outputs also available (mA, Pt 100, and Cu 10);
• Each switch can be specified with adjustable hysteresis (5 to 25°C);
• Non-pressured bellows system better resists leakage when compared to bourdon tube (pressurized) style capillary thermometers;
• Integrated heating element in bellows for winding temperature indication eliminates extra cost and complexity of accessories to simulate the winding;
• AKM bellows system provides a 260° dial deflection (angle the pointer travels from minimum to maximum) making it easier to interpret temperature reading from a distance. OPTIONS - Temperature ranges applicable for oil (liquid) or winding (winding temperature simulation does not require heated well);
• Up to 6 user adjustable switches with independent switch types;
• Mounting style, tank connection style, probe length, capillary (length, material, protective housing), compatible well (pocket);
• SCADA outputs (0-1mA, 4-20mA, Pt 100, and Cu 10), analog and digital remote indicators. 

applications

The AKM OTI/WTI has integrated control and alarm functions for temperature indication. Designed for use where the point of measurement (the well or pocket) is not easily viewed by personnel requiring separate or remote indication.

download

Technical Data Sheet - QUALITROL AP AKM OTI WTI.pdf